Module 03 / Lesson 3.5 · Self-paced learning

Review instruments, controls and failure responses

Evaluate the design of control protection without assuming two displays mean independence.

2.4 minutes · English captions · Illustrations and worked example

This lesson’s core explanations and worked-example reasoning are narrated. The table restates the example for reference; the practice activity and model answer are reading exercises.

English captions available.

Read the lesson · Download captions · Download transcript

Narration and visual explanations

Open View Technical Explanation to see each diagram, its text description and the matching narration. Standard abbreviations and numerals are used visually.

Part 1 of 4

One sensor, two functions

View Technical Explanation · Diagram 1
One sensor, two functions — diagram 1. Description below.
One sensor feeds controller and alarm in parallel; the common input creates a shared failure dependency. The left panel shows a single shared sensor branching to controller and alarm. Key points: Temperature sensor; Controller and alarm; Shared dependency.

Lesson explanation

A temperature sensor feeds both the controller and the high-temperature alarm. The diagram branches one signal into two functions. Two boxes on the drawing do not make two independent measurements. If the sensor fails low, both functions may receive the same misleading value. Whether that matters depends on the process risk and other protections. State the failure mechanism before deciding whether an independent sensor or another protective measure is necessary.

Part 2 of 4

Define the fault response

View Technical Explanation · Diagram 2
Define the fault response — diagram 2. Description below.
A sensor fault triggers a defined response and operator information; the safe response must be justified for the actual process. The left panel shows a single shared sensor branching to controller and alarm. Key points: Sensor disconnect; Defined safe response; Operator information.

Lesson explanation

The functional specification should describe the response to a detected sensor disconnect, including control behaviour and operator information appropriate to the intended use. Our teaching example proposes inhibiting heating and generating an identifiable alarm; it is not a universal safe-state instruction. Review whether that response introduces another hazard for the particular process. Distinguish an alarm that merely informs an operator from an interlock that changes operation automatically.

Part 3 of 4

Specify records and access

View Technical Explanation · Diagram 3
Specify records and access — diagram 3. Description below.
Settings, users and decision-relevant records connect to a separate computerized-system assessment; a password alone is not sufficient evidence. The left panel shows a single shared sensor branching to controller and alarm. Key points: Authorized settings; Relevant records; System-specific assessment.

Lesson explanation

If the control system creates records used for GMP decisions, identify those records and the applicable computerized-system requirements. Consider who can change a setpoint, how changes are controlled and how necessary records remain available. The European context is EU GMP Annex 11. Where relevant, also assess the applicability of FDA 21 CFR Part 11. This module flags the interface; it does not complete computerized-system validation or demonstrate compliance with either framework. A password screen by itself is not evidence of adequate access control, data integrity or record retention.

Part 4 of 4

Plan meaningful challenges

View Technical Explanation · Diagram 4
Plan meaningful challenges — diagram 4. Description below.
Verification covers normal operation, a defined fault and recovery; design review confirms feasibility rather than claiming executed results. The left panel shows a single shared sensor branching to controller and alarm. Key points: Normal response; Fault challenge; Recovery after failure.

Lesson explanation

Create a test intention for normal operation, the identified fault and recovery. For our sensor scenario, a later test should challenge the fault in a controlled way and verify the specified response and operator indication. Also consider restoration: an uncontrolled restart may be unacceptable. During DQ, check that the design and test method make the challenge feasible. The actual execution, safety controls and acceptance decision belong to approved site procedures.

Worked example

Fictional worked example — not an approved site record
ItemFictional design-review entry
FailureSensor disconnect; assess additionally plausible undetected failures
Proposed responseHeating inhibited and alarm generated, subject to process-specific review
Evidence neededFunctional specification and wiring/signal architecture
Future testControlled fault challenge plus recovery/reset verification
BoundaryNo claim of complete CSV or certified fail-safe design

Apply it · Activity 5

Draw a shared-sensor chain and write a test intention for its failure response and recovery.

Open workbook activity
Compare with model reasoning

Show the common sensor feeding both functions. Identify the fault, intended safe response, alarm information and reset/restart behaviour. Assess independence according to risk; do not demand it universally.

Knowledge check

1. Controller and alarm share one sensor. Which review is most useful?

Technical sources